Levelflex M 3 Function group "basic setup" (00)
Endress+Hauser 19
3.6 Function "probe length" (031)
Use this function to select whether the probe length was changed after factory calibration. Only then
is it necessary to enter or correct the probe length.
Selection:
• not modified
• modified
!
Note!
If "modified" was selected in the "probe length" (031) function, the probe length is defined in the
next step.
3.7 Function "probe" (032)
Use this function to select whether the probe is uncovered or covered.
If the probe is uncovered, the Levelflex can determine the probe length automatically "determine
length" (034). function. If the probe is covered, a correct entry is required in the "probe length"
(033) function
Selection:
•free
• covered
3.8 Function "probe length" (033)
With this function, the probe length can be entered manually.
3.9 Function "determine length" (034)
Use this function to determine the probe length automatically.
Due to the mounting conditions, the automatically determined probe length may be larger than the
actual probe (typically 20 .. 30 mm longer). This has no influence on the measuring accuracy. When
entering the empty value for a linerisation, please use the "empty calibration" instead of the auto-
matically determined probe length.
⇒