3 Function group "basic setup" (00) Levelflex M
22 Endress+Hauser
3.13 Function "check distance" (051)
This function triggers the mapping of interference echoes. To do so, the measured distance must be
compared with the actual distance to the product surface. The following options are available for
selection:
Selection:
•distance = ok
dist. too small
dist. too big
dist. unknown
•manual
•probe free
distance = ok
Use this function at part-covered probe. Choosing function "manual" or "probe free" at free probe.
mapping is carried out up to the currently measured echo
The range to be suppressed is suggested in the "range of mapping (052)" function
Anyway, it is wise to carry out a mapping even in this case.
!
Note!
At free probe, the mapping should be confirmed with the choice "probe free".
dist. too small
At the moment, an interference is being evaluated
Therefore, a mapping is carried out including the presently measured echoes
The range to be suppressed is suggested in the "range of mapping (052)" function
dist. too big
This error cannot be remedied by interference echo mapping
Check the application parameters (002), (003), (004) and "empty calibr." (005)
dist. unknown
If the actual distance is not known, no mapping can be carried out.
manual
A mapping is also possible by manual entry of the range to be suppressed. This entry is made in the
"range of mapping (052)" function.