Levelflex M 6 Function group "linearisation" (04)
Endress+Hauser 35
6.2 Function "linearisation" (041)
Linearisation defines the ratio of level to container volume or product weight and allows a measure-
ment in customer units, e.g. metres, hectolitres etc. The measured value in (000) is then displayed
in the selected unit.
This function is used to select the linearisation modes.
Selection:
linear
horizontal cyl
manual
semi-automatic
•table on
•clear table
linear
The tank is linear e.g. a cylindrical vertical tank. You can measure in customer units by entering a
maximum volume/weight.
You can select the "customer unit" (042). Define the volume value corresponding to the calibra-
tion in "max. scale" (046). This value corresponds to an output of 100% (= 20 mA for HART).
ENDRESS + HAUSER
E
+
100%
20
mA
0%
4
mA
kg, m
3
,ft
3
, ... = customer unit (042)
max.scale
(046)