Levelflex M 4 Function group "safety settings" (01)
Endress+Hauser 25
4 Function group "safety settings" (01)
4.1 Function "output on alarm" (010)
This function is used to select the reaction of output on an alarm.
Selection:
MIN (<= 3.6mA)
MAX (22mA)
•hold
user specific
MIN (<= 3.6mA)
If the instrument is in alarm state, the output changes as follows:
HART: MIN-Alarm 3.6 mA
PROFIBUS PA: MIN-Alarm -99999
FOUNDATION Fieldbus: MIN-Alarm -99999