3 Function group "basic setup" (00) Levelflex M
24 Endress+Hauser
3.16 Display (008)
The distance measured from the reference point to the product surface and the meas. value calcu-
lated with the aid of the empty alignment are displayed again. Check whether the values correspond
to the actual meas. value or the actual distance. The following cases can occur:
Distance correct – meas. value correct -> basic setup completed
Distance incorrect – meas. value incorrect -> a further interference echo mapping must be car-
ried out "check distance"(051).
Distance correct – meas. value incorrect -> check "empty calibr." (005)
!
Note!
After the basic setup, an evaluation of the measurement with the aid of the envelope curve
("envelope curve" (0E)" function group) is recommended.