Installation Liquiline CM442R/CM444R/CM448R
12 Endress+Hauser
4 Installation
4.1 Installation conditions
4.1.1 Mounting on DIN rail as per IEC 60715
L
CAUTION
The power unit can get very hot under full load
Burn hazard!
Avoid touching the power unit during operation.
The minimum distances to other devices must be observed.
After switching off the power unit, allow it to cool down before carrying out any work on it.
L
CAUTION
Impermissible collection of moisture in the device
Puts the safety of the user at risk!
The device has IP20 shock protection. Never allow moisture to collect in the device.
Comply with the specified ambient conditions,e.g. by installing the device in an appropriate
protective enclosure.
NOTICE
Incorrect mounting location in the cabinet, spacing regulations not observed
Possible malfunctions as a result of heat buildup and interference from neighboring devices!
Do not position the device directly above sources of heat. The temperature specification
must be observed.
The components are designed for convection-based cooling. Avoid heat buildup. Ensure
openings are not covered, e.g. by cables.
Observe the specified distances to other devices.
Physically separate the device from frequency converters and high-voltage devices.
Recommended installation direction: horizontal. The specified ambient conditions, and
particularly the ambient temperatures, only apply for horizontal installation.
Vertical orientation is also possible. However, this requires additional fixing clips at the
place of installation to hold the device in position on the DIN rail.
Recommended installation of power unit for CM444R and CM448R: to the left of the
device.