Endress+Hauser Liquistation CSF48 - Signal on Alarm; Load; Linearization;Transmission Behavior; Current Outputs, Active (Optional)

Endress+Hauser Liquistation CSF48
48 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Liquistation CSF48
Endress+Hauser 23
PROFIBUS DP
Modbus RS485
Ethernet and Modbus TCP
EtherNET/IP
Signal on alarm Adjustable, as per NAMUR Recommendation NE 43
In measuring range 0 to 20 mA (HART is not available with this measuring range):
Error current from 0 to 23 mA
In measuring range 4 to 20 mA:
Error current from 2.4 to 23 mA
Factory setting for error current for both measuring ranges:
21.5 mA
Load Max. 500
Linearization/transmission
behavior
Linear
Current outputs, active
(optional)
Span
0 to 23 mA
Signal coding EIA/TIA-485, PROFIBUS-DP-compliant acc. to IEC 61158
Data transmission rate 9.6 kBd, 19.2 kBd, 93.75 kBd, 187.5 kBd, 500 kBd, 1.5 MBd,
6MBd, 12MBd
Galvanic isolation Yes
Connectors Spring-cage terminal (max. 1.5 mm), bridged internally in the
connector (T function), M12 optional
Bus termination Internal slide switch with LED display
Signal coding EIA/TIA-485
Data transmission rate 2400, 4800, 9600, 19200, 38400, 57600 and 115200 baud
Galvanic isolation Yes
Connectors Spring-cage terminal (max. 1.5 mm), bridged internally in the
connector (T function), M12 optional
Bus termination Internal slide switch with LED display
Signal coding IEEE 802.3 (Ethernet)
Data transmission rate 10 / 100 MBd
Galvanic isolation Yes
Connection RJ45, M12 optional
IP address DHCP or configuration using menu
Signal coding IEEE 802.3 (Ethernet)
Data transmission rate 10 / 100 MBd
Galvanic isolation Yes
Connection RJ45, optional M12 (D-encoded)
IP address DHCP (default) or configuration via menu