Liquisys M CLM223/253 Commissioning
Endress+Hauser 51
a0008940
Fig. 30: Control characteristic PID controller with basic load dosing
APID with basic load
B Basic load
CPID
Commissioning
If you do not yet have any experience for setting the control parameters, set the values that
yield the greatest possible stability in the control circuit. Proceed as follows to optimize the
control circuit further:
• Increase the control gain K
p
until the controlled variable just starts to overshoot.
•Reduce K
p
slightly and then reduce the integral action time T
n
so that the shortest possible
correction time without overshooting is achieved.
• To reduce the response time of the controller, also set the derivative action time T
v
.
Control and fine optimization of the set parameters with a recorder