Liquisys M CLM223/253 Electrical connection
Endress+Hauser 21
Panel-mounted instrument measuring cable connection
To connect a conductivity sensor, connect the measuring cable in accordance with the
terminal assignment to the terminals on the rear of the device (see connection sticker).
Example of connecting a conductivity sensor
4.1.4 Alarm contact
a0008919
Fig. 13: Connection of conductive sensors
a0008918
Fig. 14: Connection of inductive sensors
a0006415
Fig. 15: Recommended fail-safe switching for the alarm contact
A Normal operating status B Alarm condition
Normal operating status:
Device in operation and no error message
present (alarm LED off)
• Relay energized
Contact 42/43 closed
Alarm condition
Error message present (alarm LED red) or
device defective or voltage-free (alarm LED off)
Relay de-energized
Contact 41/42 closed
GN WH YE
GN WH YE
BK
BK
CYK71/CPK9
83 16 15 84
231
11 12 13
PE
83
11
S
12
16
15
84
CLK5
13
GN
WH
YE
RD
WH
BU
RD
RD
BU
41
42
43
41
42
43
A
B