EasyManua.ls Logo

Endress+Hauser Micropilot FMR20 - Commissioning and operation; Installation and function check; Commissioning via SmartBlue (App)

Endress+Hauser Micropilot FMR20
40 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
System integration via Modbus protocol Micropilot FMR20 Modbus RS485
30 Endress+Hauser
8.1.2 Modbus function codes
Function code Action Register type Command type
03 (0x03) Single / multiple read Holding Register Standard
06 (0x06) Single write Holding Register Standard
16 (0x10) Multiple write Holding Register Standard
8.1.3 Modbus exceptions
Exception Number Description
MB_EX_ILLEGAL_FUNCTION 01 (0x01) Function code is not supported
MB_EX_ILLEGAL_DATA_ADDRESS 02 (0x02) Register address is not available
MB_EX_ILLEGAL_DATA_VALUE 03 (0x03) Data value is not permitted (e.g. writing of a float32 to a char8
register).
Also valid for writing to read-only registers.
8.1.4 Modbus special data types
Data type Registers
per
parameter
Description
float32
(IEEE754)
2 As a float32 consists of four bytes, a parameter with float32 as the data type must be
divided into two 16-bit words that are transmitted via Modbus. To read a float32-type
parameter, two consecutive Modbus registers therefore must be read.
Modbus register [n] Modbus register [n+1]
Byte A Byte B Byte C Byte D
float32 value
uint32 /
int32
2 The same conditions that apply for float32 data types also apply for uint32 / int32 data
types.
Modbus register [n] Modbus register [n+1]
Byte A Byte B Byte C Byte D
uint32 / Int32 value
string (char8
array)
0.5 As a single character of a character string only needs one byte, two characters are
always packed into a Modbus register. Furthermore, the length of a parameter with
string as the data type is limited to 60 characters.
Modbus register [n] Modbus register [n+1]
char8 [n] char8 [n+1] char8 [n+2] char8 [n+3]

Other manuals for Endress+Hauser Micropilot FMR20

Related product manuals