Commissioning and operation Micropilot FMR20 Modbus RS485
34 Endress+Hauser
9.2 Configuring level measurement via operating software
100%
0%
R
BD
D
L
F
E
A0045565
 27 Configuration parameters for level measurement in bulk solids
R Reference point of measurement
D Distance
L Level
E Empty calibration (= zero point)
F Full calibration (= span)
BD Blocking distance
9.2.1 Via SmartBlue
1. Navigate to: Setup → Distance unit
Select unit of length for distance calculation
2. Navigate to: Setup → Empty calibration
Specify empty distance E (distance from reference point R to minimum level)
3. Navigate to: Setup → Full calibration
Specify full distance F (span: max. level - min. level)
4. Navigate to: Setup → Distance
Shows the distance D that is currently measured from the reference point (lower
edge of flange / last sensor thread) to the level
5. Navigate to: Setup → Confirm distance
Compare the distance displayed with the actual value in order to start the recording
of an interference echo map