Micropilot FMR20 Modbus RS485 System integration via Modbus protocol
Endress+Hauser 29
7.3 Remote operation via Modbus protocol
A0046459
23 Options for remote operation via Modbus protocol
1 Computer with Modbus operating tool (customer application, terminal application, etc.)
2 Remote Transmit Unit (RTU) with Modbus (e.g. Fieldgate FXA42)
3 Memograph M RSG45
4 Modbus RS485
5 Smartphone / tablet with SmartBlue (app)
6 Transmitter with Modbus and Bluetooth® wireless technology
8 System integration via Modbus protocol
8.1 Modbus RS485 information
8.1.1 Modbus settings
The following settings can be customized via Bluetooth and Modbus.
Setting Options Default
Data bits 7,8 8
Parity Even, odd, none Even
Stop bits 1,2 1
Baud rate 1200, 2400, 4800, 9600, 19200 9600
Protocol RTU, ASCII RTU
Addressing 1 to 200 200
Minimum polling interval 500 ms