Installation Micropilot FMR51, FMR52 FOUNDATION Fieldbus
32 Endress+Hauser
6.6 Installation in bypass
1
2
2
90°
90°
A0019446
 9 Installation in bypass
1 Marking for antenna alignment
2 Tank connectors
Alighn the marker perpendicular (90°) to the tank connectors.
Measurements can be performed through an open full bore ball valve without any
problems.
After mounting, the housing can be turned 350° in order to facilitate access to the
display and the terminal compartment →  34.
6.6.1 Recommendations for the bypass pipe
Metal (no plastic or enamel coating).
Constant diameter.
Select horn antenna as big as possible. For intermediate sizes (e.g. 95 mm (3.5 in))
select next larger antenna and adapt it mechanically (for horn antennas).
Diameter difference between horn antenna and inner diameter of the bypass as small as
possible.
At any transition (i.e. when using a ball valve or mending pipe segments), no gap may be
created exceeding 1 mm (0.04 in).
In the area of the tank connections (~ ±20 cm (7.87 in)) a reduced accuracy of the
measurement has to be expected.