Operating menu Tankside Monitor NRF81
140 Endress+Hauser
Option Current range for process
variable
Lower alarm signal level Upper alarm signal level
4...20 mA US 3.9 to 20.8 mA < 3.6 mA > 21.95 mA
Fixed current Constant current, defined in the Fixed current parameter (→  140).
In the case of an error, the output current assumes the value defined in the Failure
mode parameter (→  141).
Fixed current
Navigation  Setup → Advanced setup → Input/output → Analog I/O → Fixed current
Prerequisite Current span (→  139) = Fixed current
Description Defines the fixed output current.
User entry 4 to 22.5 mA
Factory setting 4 mA
Additional information
Read access Operator
Write access Maintenance
Analog input source
Navigation  Setup → Advanced setup → Input/output → Analog I/O → Analog input source
Prerequisite Operating mode (→  138) = 4..20mA output or HART slave +4..20mA output
Current span (→  139)Fixed current
Description Defines the process variable transmitted via the AIO.
Selection None
Tank level
Tank level %
Tank ullage
Tank ullage %
Measured level
Distance
Displacer position
Water level
Upper interface level
Lower interface level
Bottom level
Tank reference height
Liquid temperature
Vapor temperature
Air temperature