Operating menu Tankside Monitor NRF81
142 Endress+Hauser
Error value
Navigation  Setup → Advanced setup → Input/output → Analog I/O → Error value
Prerequisite Failure mode (→  141) = Defined value
Description Defines the output value in case of an error.
User entry 3.4 to 22.6 mA
Factory setting 22 mA
Additional information
Read access Operator
Write access Maintenance
Input value
Navigation  Setup → Advanced setup → Input/output → Analog I/O → Input value
Prerequisite Operating mode (→  138) = 4..20mA output or HART slave +4..20mA output
Current span (→  139)Fixed current
Description Shows the input value of the analog I/O module.
Additional information
Read access Operator
Write access -
0 % value
Navigation  Setup → Advanced setup → Input/output → Analog I/O → 0 % value
Prerequisite Operating mode (→  138) = 4..20mA output or HART slave +4..20mA output
Current span (→  139)Fixed current
Description Value corresponding to an output current of 0% (4mA).
User entry Signed floating-point number
Factory setting 0 Unitless
Additional information
Read access Operator
Write access Maintenance