Tankside Monitor NRF81 Operating menu
Endress+Hauser 143
100 % value
Navigation  Setup → Advanced setup → Input/output → Analog I/O → 100 % value
Prerequisite Operating mode (→  138) = 4..20mA output or HART slave +4..20mA output
Current span (→  139)Fixed current
Description Value corresponding to an output current of 100% (20mA).
User entry Signed floating-point number
Factory setting 0 Unitless
Additional information
Read access Operator
Write access Maintenance
Input value %
Navigation  Setup → Advanced setup → Input/output → Analog I/O → Input value %
Prerequisite Operating mode (→  138) = 4..20mA output or HART slave +4..20mA output
Current span (→  139)Fixed current
Description Shows the output value as a percentage of the complete 4...20mA range.
Additional information
Read access Operator
Write access -
Output value
Navigation  Setup → Advanced setup → Input/output → Analog I/O → Output value
Prerequisite Operating mode (→  138) = 4..20mA output or HART slave +4..20mA output
Description Shows the output value in mA.
Additional information
Read access Operator
Write access -