Tankside Monitor NRF81 Commissioning
Endress+Hauser 61
9.2.3 Configuration of the 4-20mA inputs
D
E
F
C
B
A
1
1
1
1 3
2
2 4
1
HR
CDI
WP
on
SIM
2
2
3
3
4
4
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
POWER
i
B
B1-3 B4-8
1 2 3 4 5 6 7 8
A0032464
27 Possible locations of the Analog I/O modules, which can be used as a 4-20mA input. The order code of the
device determines which of these modules is actually present → 20.
For each Analog I/O module to which a 4-20mA device is connected, proceed as follows:
1. Make sure the 4-20mA devices are connected as defined by the terminal assignment
→ 26.
2. Navigate to the submenu of the respective Analog I/O module: Setup → Advanced
setup → Input/output → Analog I/O X1-3
3. Go to the Operating mode parameter (→ 138) and select 4..20mA input or
HART master+4..20mA input.
4. Go to the Process variable parameter (→ 144) and specify which process variable
is transmitted by the connected device.
5. Go to the Analog input 0% value parameter (→ 144) and define which value of
the process variable corresponds to an input current of 4 mA (see diagram below).
6. Go to the Analog input 100% value parameter (→ 144) and define which value
of the process variable corresponds to an input current of 20 mA (see diagram
below).
7. Go to the Process value parameter (→ 145) and check whether the indicated
value matches the actual value of the process variable.
A0029264
28 Scaling of the 4-20mA input to the process variable
1 Input value in mA
2 Process value
The Analog I/O submenu contains additional parameters for a more detailed
configuration of the Analog Input. For a description refer to : → 138