Levelflex M FMP40 with PROFIBUS PA Mounting
Endress + Hauser 21
Minimum distance B of the probe to the container wall:
Distance to protruding internals min. 300 mm.
Other installations
• Select the mounting location such that the
distance to internals (5) (e.g. limit switch,
struts) > is 300 mm over the entire length of
the probe, also during operation.
• Probe must within the measuring span not
touch any internals during operation. If
necessary: when using rope probes the probe
end (4) may be fixed to ensure that → ä 29!
Optimization options
• Interference echo suppression: Measurement
can be optimised by electronically tuning out
interference echoes.
L00-FMP4xxxx-17-00-00-xx-037
5
4
Wall min. distance B
Metal 100 mm for smooth walls
Plastic 100 mm, min. 300 mm to metallic components outside of the tank
Concrete 0.5 m/20", otherwise the max. possible measuring range is reduced