Levelflex M FMP40 with PROFIBUS PA Operation
Endress + Hauser 45
5.3 Local operation
5.3.1 Locking of the configuration mode
The Levelflex can be protected in two ways against unauthorised changing of instrument data,
numerical values or factory settings:
"unlock parameter" (0A4):
A value <> 2457 (e.g. 2450) must be entered in "unlock parameter" (0A4) in the
"diagnostics" (0A) function group. The lock is shown on the display by the symbol and can be
released again either via the display or by communication.
Hardware lock:
The instrument is locked by pressing the
O
and
S
and
F
keys at the same time. The lock is shown
on the display by the symbol and can only be unlocked again
via the display by pressing the
O
and
S
and
F
keys at the same time again. It is not possible to
unlock the hardware by communication. All parameters can be displayed even if the instrument is
locked.
O
and
S
and
F
press simultaneous
The LOCK_SYMBOL appears on the LCD.