Levelflex M FMP40 with PROFIBUS PA Mounting
Endress + Hauser 27
Measurement in corrosive fluids
For measurement in corrosive liquids use Levelflex M FMP41C When using plastic tanks it is also
possible to mount the probe on the outside of the tank (see Installation instructions on ä 30).
Levelflex measures the level through the plastic in both cases.
Installation in underground tanks
Use coax probe for nozzles with large
diameters in order to avoid reflections at the
nozzle wall.
L00-FMP4xxxx-17-00-00-yy-022
Installation in stilling well or bypass
A rod probe can be used for pipe diameters
bigger than 40 mm.
When installing a rod probe into a metallic
pipe with internal diameter of up to 150 mm,
you have all the advantages of a coax probe.
Welded joints that protrude up to approx. 5
mm/0.2" inwards do not influence
measurement.
L00-FMP4xxxx-17-00-00-yy-023