Mounting Levelflex M FMP40 with PROFIBUS PA
32 Endress + Hauser
Installing FMP40 with heat insulation
If process temperatures are high, FMP40 must be included in normal tank insulation to prevent
the electronics heating up as a result of heat radiation or convection.
The insulation may not exceed beyond the points labelled "MAX" in the drawing.
Installation in DN 300 nozzles
If installation in 300mm/12" nozzles is
unavoidable, installation must be carried out in
accordance with the sketch on the right.
L00-FMP4xxxx-17-00-00-en-034
pipe
150 180Ø
plate diameter
280
> 350
nozzle diameter
DN 300
> DN 400
plate
Approx. flush with
the lower edge of
the nozzle ( 50 mm).±
lower edge of
the nozzle
Process connection with adapter G ¾, G
1½, ¾ NPT or 1½ NPT
Process connection with flange
DN40...DN200
L00-FMP40xxx-17-00-00-en-003 L00-FMP40xxx-17-00-00-en-002
MAX
max. 150° C (302° F)
tank insulation
MAX
40
max. 150° C (302° F)
tank insulation