Levelflex M FMP40 with PROFIBUS PA Operation
Endress + Hauser 63
Data strings
In der Slot/Index table some data types, e.g. DS-33 are marked by an asterisk. These are data strings
according to the PROFIBUS-PA specifications part 1, Version 3.0. They contain several elements,
which are addressed by an additional subindex. The following table gives an example.
5.5.7 Scaling of the output data
The on-site display and the digital output are working independently of each other.
On-site display
The on-site display always displayes the main value V0H0 directly from the Transducer Block.
Digital output
For the digital output this value is rescaled in two steps:
L00-FMUx3xxx-05-00-00-en-001
1. In a first step, the main value is mapped to the interval [0;1]. PV_SCALE_MIN and
PV_SCALE_MAX determine the limits of this mapping.
Measured level V9H6 1 234 4 FLOAT x dynamic
Gap 1 235
Application parameter V9H8 1 236 1 UNSIGNED8 x dynamic
Gap 1 237
Tag no. VAH0 1 238 STRING x const
Profile revision VAH1 1 239 STRING x x static
Version string VAH2 1 240 STRING x const
Gap 1 241
Serial no. VAH4 1 242 STRING x x static
Distance unit VAH5 1 243 2 UNSIGNED16 x x static
Gap 1 244 -
245
Download mode VAH8 1 246 1 UNSIGNED8 x x static
Data type Subindex Typ Size [bytes]
DS-33 1 FLOAT 4
5 UNSIGNED8 1
Parameter E+H Matrix
(CW II)
Slot Index Size
[bytes]
Type Read Write Storage
Class
01
0
1
PV_SCALE_MAX
PV_SCALE_MIN
OUT_SCALE
MIN
OUT_SCALE
MAX
V0H0
AI_OUT
(V6H2)
PLC
from Transducer
block