Electrical connection Proline Promag L 400
38 Endress+Hauser
7.3 Hardware settings
7.3.1 Setting the device address
EtherNet/IP
The IP address of the measuring device can be configured for the network via DIP switches.
Addressing data
IP address and configuration options
1st octet 2nd octet 3rd octet 4th octet
192. 168. 1. XXX
↓ ↓
Can only be configured via software addressing Can be configured via
software addressing
and hardware
addressing
IP address range 1 to 254 (4th octet)
IP address broadcast 255
Addressing mode ex works Software addressing; all DIP switches for hardware addressing are set to OFF.
IP address ex works DHCP server active
For device addressing via software (→ 53)
Setting the address
1
2
3
4
1
2
3
4
1
2
ON OFF
Default Ethernet network settings
IP 192.168.1.212
Write protection
128
64
32
16
8
4
2
1
IP Address
setting
(last octet)
A0021322
‣
Set the desired IP address using the corresponding DIP switches on the I/O electronics
module.
Hardware addressing with the configured IP address is enabled after 10 s.