Operation options Proline Promag L 400
50 Endress+Hauser
1
2
3
4
1
2
3
4
1
2
ON OFF
Default Ethernet network settings
IP 192.168.1.212
Write protection
128
64
32
16
8
4
2
1
IP Address
setting
(last octet)
A0023353
Once the DIP switch has been activated, the device must be restarted
before the device uses the standard IP address.
If the standard IP address (top DIP switch No. 2 = ON) is used, there is
no connection to the EtherNet/IP network.
Software of the computer
Web browsers supported Microsoft Internet Explorer (min. 8.x)
Mozilla Firefox
Google chrome
Recommended operating systems Windows XP
Windows 7
User rights for TCP/IP settings User rights required for TCP/IP settings (e.g. for changes to IP address, subnet
mask)
Computer configuration JavaScript is enabled
If JavaScript cannot be enabled, enter http://192.168.1.212/basic.html in the
address line of the Web browser. A fully functional but simplified version of
the operating menu structure starts in the Web browser.
8.3.3 Establishing a connection
Configuring the Internet protocol of the computer
IP address 192.168.1.XXX; for XXX all numerical values except: 0, 212 and 255 → e.g.
192.168.1.213
Subnet mask 255.255.255.0
Default gateway 192.168.1.212 or leave cells empty
1. Switch on the measuring device and connect to the computer via the cable .
2. If a 2nd network card is not used: all the applications on the notebook should be closed,
or all the applications that require the Internet or network, such as e-mail, SAP
applications, Internet or Windows Explorer, i.e. close all open Internet browsers.
3. Configure the properties of the Internet protocol (TCP/IP) as defined in the table above.