Mounting Proline Prosonic Flow B 200
14 Endress+Hauser
Orientation Compact version
A Vertical orientation
A0015545
B Horizontal orientation, transmitter
head up *
A0015589
C Horizontal orientation, transmitter
head down *
A0015590
D Horizontal orientation, transmitter
head at side
A0015592
* A maximum deviation of only ±3 ° is permitted for the horizontal alignment of the
transducers.
+3°
–3°
+3°
–3°
A0016534
Inlet and outlet runs
The sensor should be mounted upstream of assemblies such as valves, T-sections, elbows etc.
where possible. As a minimum, the inlet and outlet runs shown below must be observed to
achieve the specific accuracy of the device. The longest inlet run shown must be observed if
two or more flow disturbances are present.
For the dimensions and installation lengths of the device, see the "Technical Information"
document, "Mechanical construction" section