Mounting Proline Prosonic Flow B 200
16 Endress+Hauser
Two-path version: DN 100 to 200 (4 to 8")
A
10 × DN 3 × DN
B
C D
1 2
10 × DN 3 × DN
1 2
10 × DN 3 × DN
1 2
10 × DN 3 × DN
1 2
A0015553
 4 Two-path version: minimum inlet and outlet runs with various flow obstructions
A 90 ° elbow or T-section
B Pump
C 2× 90 ° elbow 3-dimensional
D Control valve
1 Inlet run
2 Outlet run
6.1.2 Requirements from environment and process
Ambient temperature range
Transmitter –40 to +60 °C (–40 to +140 °F)
Local display –20 to +60 °C (–4 to +140 °F), the readability of the display may be impaired
at temperatures outside the temperature range.
Sensor Flange material carbon steel: –10 to +60 °C (+14 to +140 °F)
Flange material stainless steel: –40 to +60 °C (–40 to +140 °F)
Version without flange: –40 to +60 °C (–40 to +140 °F)
If operating outdoors:
Avoid direct sunlight, particularly in warm climatic regions.
System pressure
Sensor
Max. 10 bar (145 psi)
Thermal insulation
For optimum temperature and methane fraction measurement (order characteristic for
"Sensor version", option 2 "Volume flow + Biogas analysis"), make sure that heat is neither lost