Proline Prosonic Flow P 500 HART Use in protective systems
Endress+Hauser 35
Performing the test
For proof testing, use only the Current output simulation parameter (→  31) and the
Value current output parameter (→  32), as these are the only parameters approved
for testing the safety-related characteristics.
1. In the Value current output parameter (→  32), select the defined default values one
after the other.
2. Compare current at output 1 with this default value.
Comparing the current values
The current values can be compared using one of the following methods:
Measure the current of the DUT at the logic subsystem (process control system or safety-
related PLC).
Measure the current at the DUT using an external, traceably-calibrated ammeter.
Compare the current values.
Connecting the measuring equipment and external testing
Connecting the measuring equipment in the measuring circuit
External check of the passive current output
Requirements for the measuring equipment:
DC current measuring uncertainty ±0.2 %
DC current resolution10 µA
2
1
A
3
4
A0034446
 4 External verification taking the example of a passive current output
1 Automation system with current input (e.. g. PLC)
2 Power supply unit
3 Ammeter
4 Transmitter
1. Connect the ammeter to the transmitter by looping it in series into the circuit.
2. Connect the power supply unit.