Prosonic M
12 Endress+Hauser
The digital communication signal is transmitted to the bus via a 2-wire connection. The bus also provides the
auxiliary energy. Use 2-wire twisted pair cable with screen.
Refer to the following operating manuals for information on cable types, and how to set up and ground the
network:
BA00034S "PROFIBUS DP/PA: "Guidelines for planning and commissioning PROFIBUS DP/PA", PNO
Guideline 2.092 "PROFIBUS PA User and Installation Guideline" and IEC61158-2 (MBP).
BA00013S "FOUNDATION Fieldbus Overview", FONDATION Fieldbus Guideline and IEC61158-2 (MBP).
Fieldbus plug connectors For the versions with fieldbus plug connector (M12 or 7/8"), the signal line can be connected without opening
the housing.
Pin assignment of the M12 plug connector (PROFIBUS PA plug)
Pin assignment of the 7/8" plug connector (FOUNDATION Fieldbus plug)
Supply voltage HART, 2-wire
The following values are the voltages across the terminals directly at the instrument:
PROFIBUS PA
L00-FMxxxxxx-04-00-00-en-012
FOUNDATION Fieldbus
L00-FMxxxxxx-04-00-00-en-013
3
4
1
2
+–
T-Box
PROFIBUS PA
plant
ground
3
4
1
2
+–
plant
ground
L00-FMxxxxxx-04-00-00-yy-016
Pin Meaning
1 Signal +
2not connected
3 Signal -
4 Ground
L00-FMxxxxxx-04-00-00-yy-017
Pin Meaning
1 Signal -
2 Signal +
3not connected
4 Ground
1
4
3
2
+
nc
2
1
3
4
+
nc