Batch Controller RA33 Appendix
Endress+Hauser 75
Outputs Settings only needed if outputs (e.g. relay or analog out-
puts) should be used.
Universal output Settings for the universal output (current or pulse output).
Failure current 310009-00 Set the current to be output in the event of an error (e.g.
cable open circuit at the input).
Numerical value, max. 8 digits including decimal separa-
tor.
Meas.val. corrct. Here, you can correct the output current value (necessary
only if the device that carries out the further processing
cannot compensate for any measurement section toler-
ances).
Proceed as follows:
1. On the connected device, read out the displayed
value in both the upper and lower measuring range.
2. Enter the upper and lower target value and actual
value.
Start Value Lower correction value.
Target value 310051-00 Enter the lower setpoint here.
Actual value 310052-00 Here, enter the lower actual value which is displayed at
the connected device.
Full scale value Upper correction value
Target value 310054-00 Enter the upper setpoint here.
Actual value 310055-00 Here, enter the upper actual value which is displayed at
the connected device.
Diagnostics Device information and service functions for swift device
check.
ENP device name 000020-00 Please send these details with any questions about the
device.
Device name 000021-00 Please send these details with any questions about the
device.
Serial Number 000027-00 Please send these details with any questions about the
device.
Order Code 000029-00 Please send these details with any questions about the
device.
Order Identifier 000030-00 Please send these details with any questions about the
device.