EasyManua.ls Logo

Endress+Hauser RIA16 - Quick Wiring Guide; Electrical Connection

Endress+Hauser RIA16
32 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
RIA16 Wiring
Endress+Hauser 11
5.1 Quick wiring guide
Terminal assignment
a0011165-en
Fig. 7: Terminal assignment
5.2 Electrical connection
Both the terminal assignment and the connection values of the field indicator correspond to those
of the Ex-version. The device is only designed for operation in a 4 - 20 mA measuring circuit. There
must be potential equalisation along the circuits (within and outside the hazardous area).
+
+
I
Y
-
-
+
I
Y
-
3
2
+
-
OC
+
-
1a1b
+
-
2
3
+
-
1a
1b
+
+
I
Y
-
-
+
-
1a
1b
loop power
supply
active
passive
Terminal 2 and 3
Open Collector
loop power
supply
Terminal Terminal assignment Input and output
+ Measuring signal (+) 4 to 20 mA Signal input
- Measuring signal (-) 4 to 20 mA Signal input
1a, 1b Terminal for further instrumentation Support terminal
2 Digital limit switch (collector) Switch output
3 Digital limit switch (emitter) Switch output

Related product manuals