RIA16 Operating the field indicator
Endress+Hauser 15
6.3 Operating matrix
Menu Operating function Operating function Operating function
Parameter Default /
Choice
Parameter Default /
Choice
Parameter Default /
Choice
Analog input
INPUT
Curve
CURV
Signal damping
DAMP
Dec. point of measured
val.
DI DP
Linear
Quadratic
LINAR
SQRT
0 to 99 s 0 99.999
999.99
9999.9
99999
3 DEC
2 DEC
1 DEC
0 DEC
Scaling measured val. 4
mA
DI LO
Scaling measured val. 20
mA
DI HI
Measured value offset
OFFST
-9999 to
99999
0.0 -9999 to
99999
100.0 -9999 to
99999
0.0
Display
DISPL
Dimension
DIM
Dimension**
DTEXT
none
%
User-defined
NO
%
TEXT
XXXXX
Limit
LIMIT
Operating mode
MODE
Switching setpoint
SETP
off
Min.safety
with alarm
Max.safety
with alarm
Alarm
OFF
MIN
MAX
ALARM
-9999 to
99999
0.0
Hysteresis
HYST
Response delay
DELY
-9999 bis
99999
0.0 0-99 s 0
Operating
parameters
PARAM
User code
CODE
Program name
PNAME
Firmware version
FWVER
0000 to 9999 0000
NAMUR
NAMUR
NAMUR 3.6*
N_360
NAMUR 3.80*
N_380
Default
Edit
dEF
Edit
0 to NAMUR
20.5
3.60 NAMUR 3.6
to NAMUR
20.5
3.80
NAMUR 20.5*
N2050
NAMUR 21.0*
N2100
Test
TEST
NAMUR
3.80 to
NAMUR
21.0
20.50 NAMUR
20.5 to 25
mA
21.00 off
Open Collect.
Display
OFF
OUT
DISP
Service
SERV
Service code
SCODE
Parameter reset***
PRSET
- - - - Yes
No
Yes
No
*) only if “Edit” has been selected for NAMUR