Device configuration RIA16
20 Endress+Hauser
7.4.2 Program information
!
Note!
Press the + or - key to scroll horizontally through the 7 or 8-digit display values.
7.4.3 Alarm limits (NAMUR)
PARAM É NAMUR
The alarm limits are set to NAMUR values at the factory.
These values can
be used as default values (DEF) or
be edited freely (EDIT)
The following operating positions can be altered if operating item 'Edit' was selected.
The Namur limits are indicated in ascending order.
7.4.4 Test (TEST)
PARAM É TEST É Options OFF, OUT, DISP
Certain device functions can be tested automatically.
OFF (default)
Open collector: OUT
Display: DISP
Name Description
Program name 'PNAME' Displays the name of the software loaded in the device (7-digit)
!
Note!
Display cannot be edited
Firmware version 'FWVER' Displays the version of the firmware loaded in the device (8-digit)
!
Note!
Display cannot be edited
Name Description
NAMUR 3.6 Value range : 0 mA to < Namur 3.8
Default: 3.60
NAMUR 3.8 Value range : Namur 3.6 < x < Namur 20.5
Default: 3.80
NAMUR 20.5 Value range : Namur 3.8 < x < Namur 21.0
Default: 20.50
NAMUR 21.0 Value range : Namur 20.5 < x < 25 mA
Default: 21.00