EasyManua.ls Logo

Endress+Hauser RTA421 - Technical Data - Installation and Operation; Installation and Environmental Conditions; Construction and Display Features; Operational Parameters and Settings

Endress+Hauser RTA421
92 pages
Go to English
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Application
conditions
Mechanical
construction
Display and
operating level
Alarm set point
function
Installation conditions
Installation angle No limitation
Ambient conditions
Ambient
temperature
- 20 °C..+ 70 °C
Storage temp. - 20 °C..+ 70 °C
Climatic class To IEC 60 654-1 Class B3
Protection IP 20
Electrical
security
Environment < 2000 m altitude
EMC / immunity
Norm To IEC 61326, Class A (industral environment)
Safety
Norm To IEC 61010-1
Over voltage category II,
Installation area excessive current system 10 A
Construction Top hat DIN rail mounting to IEC 60715 TH 35
housing
Dimensions H: 110 mm, W: 45 mm, D: 112 mm
Weight approx. 150 g
Materials Housing: Plastic PC/ABS, UL 94V0
Electrical
connection
Keyed, plug on screw terminals, size up to 2.5 mm²
Display Operation, 1 x green (2.0 mm)
LED: Fault condition, 1 x red (2.0 mm)
Alarm set point, 2 x yellow (2.0 mm)
LC display:
Numeric display: 4 x 7 segment (6 mm)
Alarm set point condition: 2 x channel number,
4 x 1 segment
Bargraph: 10 x 1 segment
Display range 2 x 0 to 99 %
Operation 3 push button operation (-/+/E)
Mode Minimum, maximum
Switch threshold 00 to 99 %
Hysteresis 01 to 100 %
Time del
ay 00
to 99 s
Reaction time 0.4 s
Contactor
43

Table of Contents

Other manuals for Endress+Hauser RTA421