ENVIRO-TEC
15
FORM ET115.24-NOM11 (118)
MOTOR AND FAN DATA
TABLE 2A: PSC MOTORS, MODEL HLP, HLE
UNIT
SIZE
PSC MOTOR HP
(QTY)
# OF FANS FAN SPEED WATTS
2
115 VOLTS 208/230 VOLTS 277 VOLTS
AMPS
1
AMPS
1
AMPS
1
02 (1) 1/20
3
1
High 55
0.6 N/A N/AMedium 40
Low 36
03 (1) 1/20
3
1
High 61
0.6 N/A N/AMedium 45
Low 40
04 (1) 1/20 2
High 75
0.8 0.4 0.5Medium 65
Low 58
06 (1) 1/20 2
High 80
0.8 0.4 0.5Medium 68
Low 56
08 (1) 1/10 2
High 122
1.1 0.6 0.5Medium 83
Low 66
09 (1) 1/10 2
High 127
1.1 0.6 0.5Medium 86
Low 66
10 (2) 1/20 4
High 148
1.6 0.8 1Medium 128
Low 110
12 (2) 1/20 4
High 160
1.6 0.8 1Medium 139
Low 115
TABLE 2B: PSC MOTORS, MODEL HLF
UNIT
SIZE
PSC MOTOR HP
(QTY)
# OF FANS FAN SPEED WATTS
2
115 VOLTS 208/230 VOLTS 277 VOLTS
AMPS
1
AMPS
1
AMPS
1
02 (1) 1/20
3
1
High 55
0.6 N/A N/AMedium 40
Low 36
03 (1) 1/20
3
1
High 61
0.6 N/A N/AMedium 45
Low 40
04 (1) 1/20 2
High 75
0.8 0.4 0.5Medium 65
Low 58
06 (1) 1/10 2
High 121
1.1 0.6 0.5Medium 84
Low 66
08 (1) 1/6 2
High 224
2.1 1.1 0.9Medium 140
Low 66
09 (1) 1/6 2
High 230
2.1 1.1 0.9Medium 139
Low 67
10 (2) 1/10 4
High 226
2.2 1.2 1Medium 154
Low 128
12 (2) 1/10 4
High 248
2.2 1.2 1
Medium 171
Low 133
NOTES:
1. Motor electrical data is nameplate data.
2.WattsarebasedonanHLPwithPSCmotor,3rowcoil,12FPI,1"throwawaylter,0.05"ESPat115V.
3. PSC motors are not available in 208-277V on SZ02 and SZ03.
4. Motor data is subject to change and should not be used for submittal purposes. Refer to Web-Select submittal for actual ratings.
NOTES:
1. Motor electrical data is nameplate data.
2.WattsarebasedonanHLFwithPSCmotor,3rowcoil,12FPI,1"throwawaylter,0.05"ESPat115V.
3. PSC motors are not available in 208-277V on SZ02 and SZ03.
4. Motor data is subject to change and should not be used for submittal purposes. Refer to Web-Select submittal for actual ratings.