<TAGNAME> is <STATE> <TAGNAME> is <STATE> ...
will indicate the status of all of the digital inputs in four columns. Inputs which are
in the active state will appear as ON and those which are in their normal state will
appear as OFF.
<TAGNAME> is <STATE> <TAGNAME> is <STATE> ...
will indicate the status of all of the digital outputs in four columns.
<TAGNAME> is <VALUE> <DIM> LIMITS are L: <LO-LIM> <DIM> H: <HI-LIM>
<DIM>
<TAGNAME> is <VALUE> <DIM> TOTAL FLOW is <FLOW> <DIM>
<TAGNAME> TOTAL FLOW is <FLOW> <DIM>
...
will indicate the current value, dimensional units, low alarm limit, and high alarm
limit for all analog inputs that are not flow-type inputs. The precision of the values
displayed can be selected through ProView. Any flow-type analog input which is
responsible for maintaining a flow totalizer will display that flow in place of the
alarm limits. Any pulse-type digital input used for a digital flow meter will appear
here since the information being obtained by that type of flow meter is analog in
nature. In addition, pulse accumulators (volume totalizers) will appear here.
<TAGNAME> <PCT> PCT <MODE> <TAGNAME> <PCT> PCT <MODE>
...
will indicate the output percentage and mode of operation of all analog outputs.
The precision is fixed to one decimal place and will range from 0.0 to 100.0,
expressed as a percentage. The <MODE> of operation will be PID if the analog
output is currently being used in a PID loop, or PRO if the analog output is
currently being used in a Proportional scheme, otherwise it will be MAN indicating
that the analog output is under manual control.