ProNet Plus Series AC Servo User's Manual
·The setting unit is a percentage of rated torque.
·The maximum torque of the servomotor is used, even though the torque limit is set higher than the maximum torque of
the servomotor. (as is the case with the 300% factory setting)
t
Speed
Maximum torque
t
Speed
Limiting torque
Pn402
Pn401
With No Internal Torque Limit
(Maximum torque can be output)
With Internal Torque Limit
■Note:
Too small a torque limit setting will result in insufficient torque during acceleration and deceleration.
4.9.2 External Torque Limit
This function allows the torque to be limited at specific times during machine operation, for example, during press stops
and hold operations for robot workpieces.
An input signal is used to enable the torque limits previously set in parameters.
(1)Related Parameters
Forward External Torque Limit
Reverse External Torque Limit
Note: The setting unit is a percentage of rated torque (i.e., the rated torque is 100%).
(2)Input Signals
ProNet-□□□MG: CN1_41
ProNet-□□□EG-EC: manually set
Forward external torque limit
Forward internal torque limit
ProNet-□□□MG: CN1-42
ProNet-□□□EG-EC: manually set
Reverse external torque limit
Reverse internal torque limit
When using this function, make sure that there are no other signals allocated to the same terminals as /P-CL and /N-CL.