6 Technical Data page 73
ELC X-Series-V1.5-06.18-GB subject to technical alterations
Control characteristics
Type
ELC X24-210
ELC X24F-210
ELC X24B-210
ELC X24i-210
Current requirement of 24V-
supply (X805.5)
4.4 A max. for ELC control circuitry
5.4 A max. for ELC
control circuitry
output currents of X806 Pins 5 + 6 have to be added
Baud rate
PROFIBUS: 500 kBit
MODBUS: Baud rate 19200, 8 Databits, even
parity, 1 Start/Stop Bit
- -
Modbus timeout
60 s
- -
Max. number of devices per
BUS segment
recommended with PROFIBUS: 40
when operating in compliance with
ANSI/EIA/TIA-485-A-98: 50
- -
Ambient conditions
Type
ELC X24-210
ELC X24F-210
ELC X24B-210
ELC X24i-210
Humidity
max. 85%, non-
condensing
max. 95%
max. 85%, non-
condensing
Ambient operation temperature
5°C to +45°C
0°C to +55°C
5°C to +45°C
Ambient storage temperature
-20°C to +70°C during storage and transportation, before initial
operation leave at least 4 hrs at room temperature
Maximum storage period
2 years (also see paragraph 4.2)
Air flow
max. 200 m³ / h at T_A >35°C
typ. 100 m³ / h
values per module
Altitude of site
max. 4000 m above sea level
up to 2000 m above sea level without derating
2000 m to 4000 m above sea level: 1.5% / 100 m power reduction
effected by ELC-control (16800 W at 4000 m above sea level)
Certification
Type
ELC X24-210
ELC X24F-210
ELC X24B-210
ELC X24i-210
Protection
IP 54
Protection of front fan IP x4
Note: protection is only guaranteed if cables of the given diameters are
used (see paragraph 3.2.5)
EMC
EN 55011
EN 61000-3-3
EN 61000-6-2
Safety
EN 50178
UL
E349667
- -
E349667
Marine approval
- -

Table of Contents