6 Technical Data page 73
ELC X-Series-V1.5-06.18-GB subject to technical alterations
Control characteristics
Current requirement of 24V-
supply (X805.5)
4.4 A max. for ELC control circuitry
5.4 A max. for ELC
control circuitry
output currents of X806 Pins 5 + 6 have to be added
PROFIBUS: 500 kBit
MODBUS: Baud rate 19200, 8 Databits, even
parity, 1 Start/Stop Bit
Max. number of devices per
BUS segment
recommended with PROFIBUS: 40
when operating in compliance with
ANSI/EIA/TIA-485-A-98: 50
Ambient conditions
Ambient operation temperature
Ambient storage temperature
-20°C to +70°C during storage and transportation, before initial
operation leave at least 4 hrs at room temperature
2 years (also see paragraph 4.2)
max. 200 m³ / h at T_A >35°C
typ. 100 m³ / h
values per module
max. 4000 m above sea level
up to 2000 m above sea level without derating
2000 m to 4000 m above sea level: 1.5% / 100 m power reduction
effected by ELC-control (16800 W at 4000 m above sea level)
Certification
IP 54
Protection of front fan IP x4
Note: protection is only guaranteed if cables of the given diameters are
used (see paragraph 3.2.5)
EN 55011
EN 61000-3-3
EN 61000-6-2