2119167-07-09/23 (translation of the original operating instructions)
Operating Instructions Safety Systems
MGB-L1…-AR.-… / MGB-L2…-AR.-… and MGB-L1…-AP.-… / MGB-L2…-AP.-…
EN
12. Electrical connection
WARNING
In the event of a fault, loss of the safety function due to incorrect connection.
Ì To ensure safety, both safety outputs (FO1A and FO1B) must always be evaluated.
Ì The monitoring outputs must not be used as safety outputs.
Ì Lay the connecting cables with protection to prevent the risk of short circuits.
CAUTION
Risk of damage to equipment or malfunctions as a result of incorrect connection.
Ì The inputs on a connected evaluation unit must be positive switching, as the two outputs on the safety
switch deliver a level of +24V in the switched-on state.
Ì All the electrical connections must either be isolated from the mains supply by a safety transformer
according to EN IEC 61558-2-6 with limited output voltage in the event of a fault, or by other equiv-
alent insulation measures.
Ì All electrical outputs must have an adequate protective circuit for inductive loads. The outputs must
be protected with a free-wheeling diode for this purpose. RC interference suppression units must
not be used.
Ì Power devices which are a powerful source of interference must be installed in a separate location
away from the input and output circuits for signal processing. The cable routing for safety circuits
should be as far away as possible from the cables of the power circuits.
Ì To prevent EMC problems, it is imperative you follow the chapter 12.5. Notes on cable laying on page
25. Follow EMC notes on devices in the immediate vicinity of the MGB system and their cables.
Ì In order to avoid EMC interference, the physical environmental and operating conditions at the instal-
lation site of the device must comply with the requirements according to the standard DINEN60204-
1:2006, section 4.4.2 (EMC).
Important!
Ì If the device does not appear to function when the operating voltage is applied (e.g. green Power
LED does not illuminate), the safety switch must be returned to the manufacturer.
Ì To ensure the stated degree of protection is achieved, the cover screws must be tightened to a
tightening torque of 1 Nm.
Ì Tighten screw for the cover for the auxiliary release to 0.5 Nm.