25
2119167-07-09/23 (translation of the original operating instructions)
Operating Instructions Safety Systems
MGB-L1…-AR.-… / MGB-L2…-AR.-… and MGB-L1…-AP.-… / MGB-L2…-AP.-…
EN
12.4. Requirements for connecting cables
CAUTION
Risk of damage to equipment or malfunctions as a result of incorrect connecting cables.
Ì On the use of other connection components, the requirements in the following table apply. EUCHNER
provides no warranty for safe function in case of failure to comply with these requirements.
Observe the following requirements with respect to the connecting cables:
Parameter Value Unit
Conductor cross-section, min. 0.13 mm²
R max. 60 W/km
C max. 120 nF/km
L max. 0.65 mH/km
12.5. Notes on cable laying
Lay all MGB connecting cables in a common cable harness.
PLC
+ 24 V DC
cabinet
0 V
MGB-L.-...
FI1A/
FI1B
FO1A/
FO1B
UB 0V UA 0V
Important: lay cables in a common harness
Fig. 15: Stipulated cable laying