1. 400 V GRID CONNECTION TERMINAL BLOCK:
- Ground GRID: Max section: 95 mm², allows connection of the ground terminal
- Neutral GRID: Max Section: 95 mm², allows connection of the neutral terminal
- Ph1 GRID: Max section: 95 mm², allows connection of the phase 1 terminal
- Ph2 GRID: Max section: 95 mm², allows connection of the phase 2 terminal
- Ph3 GRID: Max section: 95 mm², allows connection of the phase 3 terminal
2. ARU EXT: Maximum section: 2,5 mm², allows connection of an external ARU button, voltage 24
Vdc, 10 mA max current.
3. CAN: Maximum section 2,5 mm², can connect the CAN communication (terminal of 1 input/3
outputs), voltage 10 Vdc, 50 mA max current.
4. BUS CAN shield: Maximum section 2,5 mm², to connect the CAN communication cable shield.
5. 24 Vdc: (for floor sensor) Maximum section 2,5 mm², Orange = +24 V, Blue = GND, 24 Vdc voltage,
7 A max current.
6. RS485: (for floor sensor) Maximum section 2,5 mm², allows connection of the RS485/MODBUS
communication (terminal of 1 input/3 outputs), voltage 10 Vdc, 50 mA max current.
7. RS485 shield: Maximum section 2,5 mm², to connect the RS485 communication cable shield.
8. SERVICE SOCKET (230 Vac): Allows connection of the 230 Vac equipment within the limit of 6 A,
230 Vac voltage, 16 A current (protect with the circuit breaker and differential D3).
9. 230 Vac terminal block: Max Section: 2,5 mm², used to connect 230 Vac equipment within the
limit of 6 A, 230 Vac voltage, 16 A current (protect with the circuit breaker and differential D3).
10. SATTELITES OPTION: Max Section: 35 mm², used to connect a DC satellite, 600 Vdc voltage,
125 Adc current.
11. D9: E/F 230 Vac Home Plug head Circuit Breaker. 16 A, curve C (Circuit Breaker + 30 mA
differential type A).
12. D3: 230 Vac control head circuit breaker, 16 A, curve C (Circuit Breaker + 30 mA differential type
A).
13. D1'': Circuit breaker position sensor D1.
14. D1'' ': Transmission coil that allows D1 to deactivate.
15. D1: power head breaker, 100 A, 4-pole, D-curve.
16. D7 ': Differential circuit breaker 30 mA, type A APR for AC output 43 kW.
17. D7: thermal magnetic circuit breaker 80 A, curve D for the 43 kW AC output (D7 is supplied with
D1 series).
18. K7: power contactor, AC1/75 A 4-pole, that cuts power to the 43 kW AC.
19. K9: power contactor, AC1/26 A 3-pole, that cuts off power to the single-phase E/F home socket.