B680H 18 732719 - Rev.D
Translation of the original instructions
ENGLISH
24
When this function is activated, an open or close command is only carried out after the
safeties have been disengaged.
Y = active
no = disabled
25
A.D.M.A.P. function
When this function is activated, the result is operation of safeties compliant with French
regulations.
Y = active
no = disabled
26
When this function is activated, the CLOSING SAFETIES during closing stop and reverse
movement when they are disengaged, otherwise they reverse immediately.
Y = stops and reverses when
disengaged.
no = reverses immediately.
27
DO NOT CHANGE
no
28
DO NOT CHANGE
no
29
DO NOT CHANGE
no
30
When this function is activated, the LOOP1 commands are prioritised rather than the LOOP2
commands.
Y = active
no = disabled
A0
HOLD CLOSE / HOLD OPEN function
When this function is activated, the automated system will monitor the position of the beam
at set intervals (see parameter
A1
). If the beam is not completely closed or completely open
(depending on the logical condition of the board), the automated system will command a
CLOSE or OPEN movement to bring the beam back to the correct position, for a maximum
of 3 seconds. If, when the 3 seconds have elapsed, the bar does not go back to completely
closed/open position (e.g. because the bar is blocked), the function will be disabled until the
next OPEN command is received.
Y
A1
HOLD CLOSE / HOLD OPEN function activation time
This parameter indicates the time interval between two activations of the HOLD OPEN /
HOLD CLOSE function, expressed in minutes. (from
00 to 99)
60
r1
Loop 1 frequency reading
This menu item lets you verify the reading of the current oscillation frequency of the loop con-
nected to the Loop 1 input. The indication should be read as follows:
First digit: tens (kHz)
Second digit: units (kHz)
Decimal point: hundreds (kHz)
For example, the reading
05. refers to a reading of 105 kHz
Read-only parameter
r2
Loop 2 frequency reading
This menu item lets you verify the reading of the current oscillation frequency of the loop con-
nected to the Loop 2 input. (see parameter
r1 for explanations on how to read the indicated
value)
Read-only parameter
F1
Loop 1 frequency selection
This parameter lets you set an oscillation frequency specific to the loop connected to the Loop
1 input, or lets the system choose the most adequate setting among the 4 available.
A Automatic selection
1-2-3-4 Frequency 1-2-3-4
Note: When you exit the ADVANCED programming menu after having changed the loop
operation frequency setting, the system will be recalibrated. This will provide an updated
frequency reading once you re-enter the menu to consult the values of parameters
r1 or r2
A
F2
Loop 2 frequency selection
This parameter lets you set an oscillation frequency specific to the loop connected to the Loop
2 input, or lets the system choose the most adequate setting among the 4 available.
A Automatic selection
1-2-3-4 Frequency 1-2-3-4
Note: When you exit the ADVANCED programming menu after having changed the loop
operation frequency setting, the system will be recalibrated. This will provide an updated
frequency reading once you re-enter the menu to consult the values of parameters
r1 or r2
A
h1
LOOP 1 holding time
Is used to set presence time on loop 1. When this time has elapsed, the board will self-cali-
brate and signal “loop clear” (LED DL3 off). When the board is turned on, an automatic reset
is carried out.
Y 5 minutes
no in nite
no
h2
LOOP 2 holding time
Is used to set presence time on loop 2. When this time has elapsed, the board will self-cali-
brate and signal “loop clear” (LED DL4 off). When the board is turned on, an automatic reset
is carried out.
Y 5 minutes
no in nite