Power supplies
94
2.
POWER SUPPLIES
Regenerative regulated power supplies
72
DDS
HARDWARE
Ref.1310
Operating cycles
Load cycle S1
Continuous duty. Operation with constant load and long enough to
achieve thermal balance.
Load cycle S6-40%
Periodic uninterrupted duty cycle with intermittent load. Succession
of identical duty cycles, each with a running period under constant load
and another period without load. There is no rest period. The 40% run-
ning factor indicates that for a 10 minute cycle, it works at constant power
for 4 minutes P S6-40% and without load for 6 minutes (0.4 x rated cur-
rent Pn).
Cycle at Pmax without previous load
Periodic intermittent duty. Succession of identical duty cycles, each with a
rest period. The 40% running factor means that for a 10 minute cycle, it
works at 1.6xPn for 4 minutes and it rests (no power) for 6 minutes.
F. H2/32
Load cycle S1.
F. H2/33
Load cycle S6-40%.
F. H2/34
Cycle at Pmax without previous load.
LOAD CYCLE S6-40%POWER
TIME
0.4xPN
PN
PS6-40
PMAX
10 MIN
4 MIN
CYCLE AT Pmax WITHOUT PREVIOUS LOAD
POWER
1.6xPN
PN
10 MIN
4 MIN
TIME