Parameters menu
Press the programming button “M” (detail 2 - fig. 1) for 5 seconds to access the parameters menu. The
parameter “u01” is displayed: identified by the message SET 01. Press the button “P” (detail 5 - fig. 1)
to scroll the list of parameters.
Just press the + and - buttons (details 4 and 6 - fig. 1) to modify the value of a parameter: the modification
will be automatically stored. After modifying the parameter, it is necessary to wait 3 seconds: the data
flashes and is stored.
Table 1
Parameters Description Range Default
u01
Delivery setpoint adjustment 30 - 80 °C 80 °C
u02
Burner max. power 1 - 5 5
u03
Burner operation methods (see par. 3.1) 0 - 2 0
Press the "operation mode selection - M" button (detail 2 – fig.1) for 5 seconds to exit the menu.
Service parameters Menu
Press the programming button “P” (detail 5 - fig. 1) for 10 seconds to access the parameters menu. The
parameter “t01” is displayed: identified by the message SET 01. Press the button “P” (detail 5 - fig. 1)
to scroll the list of parameters.
To modify the value of a parameter just press the + and - buttons (details 4 and 6 – fig. 1): the change
will be automatically stored. After modifying the parameter, it is necessary to wait 3 seconds: the data
flashes and is stored.
Table 2
Parameters Description Range Default
t01
Pellet loading function 0=Disabled, 1=Enabled 0=Disabled
t02
Delivery probe 0=Disabled, 1=Enabled 1=Enabled
t03
Fan setpoint in Lighting 0-200 Pa 51 Pa
t04
Auger activation time in Lighting 0-100 (1=4 seconds) 12
t05
Adjustment calculation timer(Only with Modulating burner
operation with delivery Probe)
0-100 seconds 5 seconds
t06
Ramp function timer 0-100 seconds 80 seconds
t07
Period (activation+deactivation time) with auger operating
(from Power 1 to Power 5)
0-50 seconds 10 seconds
t08
Fan setpoint at Power 1 0-200 Pa 38 Pa
t09
Auger activation time at Power 1 0-100 (100=10 seconds) 28
t10
Fan setpoint at Power 2 0-200 Pa 74 Pa
t11
Auger activation time at Power 2 0-100 (100=10 seconds) 38
t12
Fan setpoint at Power 3 0-200 Pa 133 Pa
t13
Auger activation time at Power 3 0-100 (100=10 seconds) 46
t14
Fan setpoint at Power 4 0-200 Pa 150 Pa
t15
Auger activation time at Power 4 0-100 (100=10 seconds) 53
t16
Fan setpoint at Power 5 0-200 Pa 170 Pa
t17
Auger activation time at Power 5 0-100 (100=10 seconds) 56
t18
Burner operation selection (Only with Delivery Probe) 0=On/Off, 1=Modulating 0=On/Off
t19
Post-Ventilation time 2 0-100 (100=10 seconds) 99
Press the programming button “P” (detail 5 - fig. 1) for 10 seconds to exit the menu.