PAGE/B1
AppendixBPROINERTValveBestPractices
ThisappendixisintendedtoserveasabestpracticesguideforaddressingproblemsrelatedtothePROINERTValve.
B.1ReportingValveFailures
Aftereachfillsession,valvesfailingtoperformasintendedshouldbereportedbacktoFikeCorporation.APROINERT
ValveFailureReport(SeeAppendixB.4)shouldbefilledoutbythepersonperformingtheinitialfill/recharge
operation.Thereportshouldbeemailedtoproinertvalve@fike.com.
B.2AddressingValveNeckLeaks
Ifavalveisleakingfromtheneck,removethevalvefromthecylinderandattempttodothefollowing:
CleanvalvethreadsbyremovingtheremainderofTeflontapeandthreadsealant.
Makesureanyhangingburrsorbrassmaterialfromthethreadsisremoved.
Tapethe
valveandapplythreadsealantasindicatedinSection3.2.
Torquethevalveintoacylinder.
Gopasttheoriginalthreaddepthprovideditiswithinthemin/maxgaugelimits.
Fillthecylinderasperinstructionsprovidedinthismanual.
ReturnthevalvetoFikeCorporation
ifitleaksevenafterfollowingtheabovementionedprocedure.
B.3InspectingIncomingCylinders
AreceivinginspectionofincomingcylindersshouldbeperformedanddocumentedusingthefollowingsetofNGTplug
gauges(B.3.1):
L1Gauge
L9Gauge
Crest CheckGauge
Itisrecommendedthata randomsampleof13cylindersbeinspectedfromeachlotreceivedforNGTspecification
conformance.APROINERTCylinderInspectionReport(SeeAppendixB.5)shouldbefilledoutbytheperson
performingtheinspection.Thereportshouldbeemailedtoproinertvalve@fike.com.
B.3.1 NGTPlugGauges
