Doc.P/N06312
Rev.11/March2020
PAGE/3
2.1 EquipmentCalibration
AprogramwillbeestablishedbytheFikeauthorizedfillingstationtoassurethattestingandmeasuringequipment
usedintheproductionand/orinspectionprocessiskeptclean,maintainedingoodworkingorder,andiswithin
calibration.
Thefollowingcalibrationfrequencieswillbeadheredtoatminimum:
CalibrationSchedule
Frequency
Onceevery
6months
Onceevery
12months
ScalesX
Pressuregauges X
Leakstandards X
ThermometersX
ThermocouplesX
WrenchesX
Equipment Whensubjectedtoabuse,
suchasbeingdroppedor
struckwithanobject,or
whenitsaccuracyis
questionable.
Calibrationmaybeperformedbythesalesoutletoranoutsidelaboratory.Calibrationwillbebycomparisonwitha
standardthatistraceabletotheapplicableUSorforeignnationalstandard.TheFikeauthorizedfillingstationwill
maintaincertificationofcalibrationuntilthenextsucceedingcertification.