PAGE/2 Doc.P/N06‐312
Rev.11/March2020
Item6: ValveFillingAdaptor(P/NIG71‐064)–Adaptorrequiredtokeepthevalveinthe“open”positionduringthe
fillingoperation.
Item7: FillAdaptor(FasTest®METHP0198Aorequivalent)–Adaptorrequiredtoconnectthefillhosetoa
PROINERTcontainervalve.
Item8: Fittings,Valves,andHoses,asRequired–ComponentsessentialtothefunctionalityofPROINERT
cylinders.
Musthaveaminimumworkingpressureof6,000psi(415bar).
Item9: ThermometerorThermocouple–Instrumentsusedtomeasuretemperature.Mustbeaccurateto±2.0F
(±1.0C)andlocatedinthePROINERTfillingarea.
Item10: PressureGaugeAssembly(P/NIG71‐125)–Assemblythatincludesa0‐5,000psi(0‐345bar)pressuregauge
withanaccuracyof0.1%offullscalereading,calibratedin5psi(.4bar)incrementsorless,withallthe
fittings,adapters,andO‐ringsattachedtoproperlyconnecttothecontainer.
Item11: Pressurevs.TemperatureChart–ChartdetailingtherelationshipsofIG‐55,IG‐100,andIG
‐541pressurevs.
temperature.SeeAppendixA.2forinformation.
Item12: ValveLockoutTool(P/NIG71‐235)–Toolrequiredtomechanicallylockthevalveinthe“closed”positionto
preventadischargewhenremovingthefillhoseandinstallingthedischargeportrecoilcap.
Item13: LogBook–Permanentrecordcontainingthefollowinginformation(seeAppendixA.3forexample):
o Datefilled
o Customer
o ValveLotNumber
o ContainerSerialNumber
o Initialfillorrecharge
o Containerpressure
o Leaktestresults
o Name/initialsofpersonperformingtheinitialfill/rechargeprocedure
Item14: LeakDetector–Devicecapableofdetectingaminimumleakrateof1.26x10
‐3
cc/sec(Argon).
Suggested:LacoTechnologiesModelLHHHLD‐3000LeakDetectororequivalent.
Item15: LeakStandard–Criterionforcalibratingtheleakdetector,capableofbeingsettotheminimumrequired
leakrateof1.26x10
‐3
cc/sec.
Item16: Scale–Apparatuscapableofaccuratelyweighingtowithin±0.5lbs(0.2kg),withatotalrangegreaterthan
themaximumchargedcontainerweightofapproximately600lbs(272kg).
Item17: VacuumPump–Devicecapableofpullingavacuumof25"to27"watercolumn.