6 - Instruments
User interface
1. Embedded Web User Interface
Accessible via Wi-Fi by using any WLAN enabled standard device
(PC, smartphone, tabled,….)
• Enables single inverter parameters settings (Aurora Manager Em-
bedded)
• Updating of the inverter rmware.
2. Local display
• Just for reading settings
• Enabled setting RS485 ports addresses and MPPT functioning mode
Available on request (it is an accessory)
3. Aurora Manager Lite
• Mainly for service purpose
• Local monitoring of the inverter.
Advanced conguration of the inverter (INSTALLER access level)
• Updating of the inverter rmware.
• In order to use the software a connection must be established be-
tween the PC and the inverter (by means of an RS485 communica-
tion line) using a PVI-USB-RS485_232 signal converter.
4. Mobile app and web portal Aurora Vision
• Remote monitoring of the inverter.
Measurement tolerance
The data supplied by the inverter may differ from measurements taken
by certied measuring instruments (e.g. output meters, multimeters and
grid analysers); since the inverter is not a measuring instrument it has
wider tolerances for the measurements it makes.
The tolerances are generally:
±5% for real-time measurements with output power below 20%
±3% for real-time measurements with output power above 20%
±4% for all statistical data.