158
000879AG-F
8 - Maintenance
Procedure for dismantling the Inverter
To dismantling and disassemble the appliance, refer to the chapters:
Mounting on a vertical or horizontal support
Follow the indications for the mounting procedure but in the reverse order
Perform the steps for “Inverter switch-off” based on the model, before removing one of the
two wiring boxes or the inverter itself.
Never open the wiring boxes in the case of rain, snow or a level of humidity >95%.
Always carefully seal all unused openings.
Even though the device is equipped with an anti-condensation valve, air
with extremely high levels of humidity can lead to the creation of conden-
sation inside the inverter.
As the inverter is almost completely insulated from the outside, conden
-
sation can also form after maintenance interventions in certain weather
conditions.
During dismantling must be installed caps on interface quick connectors on the inverter parts
that are installed and exposed to the elements.
IP65