BOOK0795-F
19
If the fuse is not blown, the internal overload monitor may have shut down the controller. The overload mon-
itor will shut down the controller if the motor armature current exceeds 120% of rated for a length of time of con-
tinuous operation. The length of time is determined by the amount of the overload. If the overload monitor trips,
reset the controller by initiating a Stop command, removing the overload, and then initiating a Run command to
restart. Repeated shutdown indicates an overload condition (mechanical or electrical) which must be removed.
Refer to the Troubleshooting Table (Table 6).