FIRECLASS Fire Alarm Control Panels 5 Wiring Reminders
Fault Finding Guide Doc. version 2 21
5 Wiring Reminders
Summary of EOL and Alarm Resistors used with various
Modules.
For full information refer to the individual device docu-
ment.
FIM 801/2 Sounder EOL 2.7k.
Supervised I/P EOL 10k /
Alarm 2k
RBus Terminate 150Ω at FIM
and 120Ω at last device
on Bus
410CIM EOL 200Ω / Alarm 100Ω
410DIM EOL 4k7
410MIM EOL 200Ω / Alarm 100Ω
410MIO EOL 330Ω / Alarm 150Ω
410DDM EOL 4k7 / Alarm 560Ω
410QIO EOL 3k3 / Alarm 680Ω
410QMO EOL 27k
410TSM EOL 3k3 / Alarm 680Ω
410SNM EOL 27k Note: 0.5w
410SIO EOL 3k3 / Alarm 680Ω
SB520 EOL 270Ω Note: 6w